Cummins Quiet Connect Liquid Cooled 80kw

Cummins Quiet Connect Liquid Cooled 80kw
Product features
Engine
• Natural gas/propane 1800 rpm engine
• Engine air cleaner – normal duty
• Electronic governor, isochronous
• Engine starter, 12 VDC motor
• Shutdown – low oil pressure
• Extension – oil drain
• Engine oil – included

Cummins Quiet Connect Liquid Cooled 80kw

GENERATORS
Cummins Quiet Connect Liquid Cooled 80kw
Features and benefits
Robust product design and testing – The generator is designed to operate under extreme environmental
conditions including cold weather starts at as low as -40 oF when equipped with the necessary accessories.
The generator is tested and certified per the latest EPA, UL and IBC Seismic standards and is capable of
meeting NFPA 110 requirements when equipped with the necessary accessories and properly installed.
Flexible exercise mode – The innovative, flexible exercise mode enables the generator to exercise at a
time, frequency and duration that suits the customer’s preference – as little as 2 minutes every 6 months –
reducing unnecessary fuel consumption, emissions and noise.
Advanced enclosure design – The aesthetically appealing enclosure incorporates special designs that
deliver the quietest generator of its kind. Aluminum material plus durable powder coat paint provides the
best anti-corrosion performance. The generator set enclosure has been evaluated to withstand 180 mph
wind loads in accordance with ASCE 7-10. The design has hinged doors to provide easy access for service
and maintenance.
Control system – The PowerCommand® electronic control is standard equipment and provides total
generator set system integration including automatic remote starting/stopping, precise frequency and
voltage regulation, alarm and status message display, output metering, auto-shutdown at fault detection and
NFPA 110 level 1 compliance.
Self-diagnostics and easy service – The PowerCommand® electronic control provides industry- leading
self-diagnostic capabilities. In addition, critical components of the generator are designed to ensure
service and preventive maintenance can be completed in a short period of time.
Weight, size, and sound level
Weight: 2782 lbs. (1262 kg)
Size: Length 118.7 in (3016 mm), width 40.0 in (1016 mm), height 58.3 in (1480 mm)
Sound: 73 dB(A) at 23 ft. (7 m) with sound level 1 enclosure
Series Model Phase Voltage (V) Frequency (Hz)
Rated amps1
(NG/LPV fuel)
Circuit breaker
(Amps)
RS80 C80N6
1 120/240 60 333/333 125-400
3 120/208 60 278/278 125-400
3 120/240 60 241/241 70-250
3 277/480 60 120/120 150
1Derating guidelines: Engine power available up to 1829 m (6000 ft.) at ambient temperatures up to 40 °C (104 °F).
Above these elevations derate at 4% per 305m (1000 ft.) and 2% per 10 °C above 40 °C (104 °F